FMMC 04-18 – MEDICAL GAS ALARMS
Effective: June 11, 1998
Reviewed: November 28, 2012
Revised: April 12, 2017, January 19, 2023
INFORMATION
Medical gases are part of the Life Support Systems. Included are medical oxygen, nitrogen, nitrous oxide, medical compressed air, and vacuum. It is important to respond to alarms for these systems since they indicate an abnormal condition which could affect patient care. Emergency procedures must be implemented immediately to correct the problem.
POLICY
Alarms received in H-64 or via phone from persons in user areas must be answered immediately. Appropriate personnel must be notified and/or vendors to restore the system to normal in the shortest possible time.
PROCEDURES
- Medical Oxygen - If line pressure drops below 40 pounds per square inch, an alarm will activate indicating insufficient pressure. The dispatcher shall notify personnel as follows:
- Maintenance person on duty should call one of the managers listed below as well as Lisa Wright and Derek Crouse:
Days |
Evenings |
|
---|---|---|
Chris Buford |
859-285-0401 |
859-285-0401 |
Shawn Skeese |
859-333-2754 |
859-333-2754 |
AND |
|
|
Lisa Wright |
859-323-6921 |
408-203-2611 |
Derek Crouse |
502-803-0473 |
502-803-0473 |
- The maintenance person assigned will check the system to determine the cause of the problem. If there are no obvious leaks in the system or other reasons for the pressure problem, maintenance should notify Oxygen supplier for immediate assistance at 800-772-9247. GS Tank account: 2025737. Chandler Tank account: 8523715
- If oxygen low level alarm sounds, it is necessary to call the vendor, Prax Air to confirm replenishment of the oxygen supply in the main tank, See note 3 for phone number and associated account numbers for each location.
MEDICAL GAS ALARM PANEL INFORMATION
Module |
Type of alarm |
Description - Source of Problem |
Action - See Notes |
Location |
---|---|---|---|---|
1 |
Air Line Pressure Low |
Medical Air compressors - Below 40 PSI |
1 & 2 |
G502 |
1 |
Air Line Pressure High |
Medical Air compressors - Above 60 PSI |
1 |
G502 |
1 |
Air Dew Point High |
Medical Air compressors - Above 39 F |
1 & 2 |
G502 |
1 |
Air Carbon Monoxide High |
Medical Air compressors - Above 10 PPM |
1 & 2 |
G502 |
1 |
Air Reserve Compressor Run |
Medical Air compressors - 3rd back up pump on |
1 |
G502 |
1 |
Future |
|
|
|
2 |
Medical Air High Temp #1 |
Med Air Compressors - Compressor #1 out - Exhaust of pump over 275 F. |
1 |
G502 |
2 |
Medical Air High Temp #2 |
Med Air Compressors - Compressor #2 out - Exhaust of pump over 275 F. |
1 |
G502 |
2 |
Medical Air High Temp #3 |
Med Air Compressors - Compressor #3 out - Exhaust of pump over 275 F. |
1 |
G502 |
2 |
Vacuum Line Low |
Med Vac. Pumps - Below 12 in Hg |
1 |
G502 |
2 |
Vacuum Reserve Pump Run |
Med Vac. Pumps - 3rd back up pump on |
1 |
G502 |
2 |
Future |
|
|
|
3 |
CO2 Line Pressure Low |
Carbon Dioxide Manifold - Less than 40 PSI |
1 |
G059 |
3 |
CO2 Line Pressure High |
Carbon Dioxide Manifold - Above 60 PSI |
1 |
G059 |
3 |
CO2 Secondary Supply In Use |
Carbon Dioxide Manifold - Switched Bank |
1 |
G059 |
3 |
CVAC Line Vacuum Low |
Centralized Smoke Evacuation - Pump failure / Possibly off / Line rupture |
1 |
G502 |
3 |
Future |
|
|
|
3 |
Future |
|
|
|
4 |
Nitrogen Line Pressure High |
Nitrogen Manifold - Line Pressure Above 195 PSI |
1 |
G059 |
4 |
Nitrogen Line Pressure Low |
Nitrogen Manifold - Line Pressure Less than 140 PSI |
1 |
G059 |
4 |
Nitrogen Secondary Supply In Use |
Nitrogen Manifold - Switched Bank |
1 |
G059 |
4 |
Nitrous Oxide Line Pressure High |
Nitrous Oxide Manifold - Above 60 PSI |
1 |
G059 |
4 |
Nitrous Oxide Line Pressure Low |
Nitrous Oxide Manifold - Less than 40 PSI |
1 & 2 |
G059 |
4 |
N2O Secondary Supply In Use |
Nitrous Oxide Manifold - Switched Bank |
1 |
G059 |
|
|
|
|
|
1 |
Oxygen Liquid Level Low |
Bulk O2 - Liquid Level Lower than 121.9 inches |
1 |
O2 PAD |
1 |
Oxygen Reserve Low |
Bulk O2 - Reserve Lower than 99.8 inches |
1 & 2 |
O2 PAD |
1 |
Oxygen Reserve In Use |
Bulk O2 - Main tank switched to reserve tank |
1 & 2 |
O2 PAD |
1 |
Reserve O2 Vessel Pressure Low |
Bulk O2 - Critically Low on O2 |
1 & 2 |
O2 PAD |
1 |
Oxygen Line Pressure Low |
Bulk O2 - Line Pressure low, below 45 |
1 |
O2 PAD |
1 |
Oxygen Ling Pressure High |
Bulk O2 - Line Pressure high, above 65 |
1 |
O2 PAD |
2 |
Oxygen Line Pressure Low |
Bulk O2 - Line Pressure low, below 45 |
1 |
O2 PAD |
2 |
Oxygen Line Pressure High |
Bulk O2 - Line Pressure high, above 65 |
1 |
O2 PAD |
2 |
Nitrogen Pressure High |
Nitrogen Manifold - Line Pressure Above 195 PSI |
1 |
HA064C |
2 |
Nitrogen Pressure Low |
Nitrogen Manifold - Line Pressure Less than 140 PSI |
1 |
HA064C |
2 |
Nitrous Oxide Line Pressure High |
Nitrous Oxide Manifold - Above 60 PSI |
1 |
HA064C |
2 |
Nitrous Oxide Line Pressure Low |
Nitrous Oxide Manifold - Less than 40 PSI |
1 |
HA064C |
3 |
Air Line Pressure High |
Medical Air compressors - Above 60 PSI |
1 |
HA3001 |
3 |
Air Line Pressure Low |
Medical Air compressors - Below 40 PSI |
1 & 2 |
HA3001 |
3 |
Medical Air Alarms |
Medical Air Compressors - System Alarms |
1 |
HA3001 |
3 |
Evacuation Low |
Med Evacuation Vac - Below 12 inches Hg |
1 |
HA3001 |
3 |
Nitrous Oxide Reserve In Use |
Nitrous Oxide Manifold - Switched Bank |
1 & 2 |
HA064 |
3 |
Nitrogen Reserve In Use |
Nitrogen Manifold - Switced Bank |
1 |
HA064 |
4 |
Vacuum Line Low |
Med Vac. Pumps - Below 12 inches Hg |
1 & 2 |
HA3001 |
4 |
Future |
|
|
|
4 |
Future |
|
|
|
4 |
Future |
|
|
|
4 |
Future |
|
|
|
4 |
Future |
|
|
|
5 |
Nitrous Oxide Reserve In Use |
Nitrous Oxide Manifold - Switched Bank |
1 & 2 |
H047 |
5 |
Nitrous Oxide Line Pressure Low |
Nitrous Oxide Manifold - Less than 40 PSI |
1 & 2 |
H047 |
5 |
Future |
|
|
|
5 |
Future |
|
|
|
5 |
Future |
|
|
|
5 |
Future |
|
|
|
For Good Samaritan Hospital, all monitored gasses SEE NOTES 1 & 2.
B031A and C110L main panel locations
Medical Air B031
Medical Air C125
Medical Vac B031
Medical Vac C125
Evac Vac B150
Tank Manifolds - C106A and A014
|
NOTES |
|
---|---|---|
1 |
Notify FMMC, 859-323-6281 or 859-323-6285 |
|
2 |
Notify FMMC, 859-323-6281 or 859-323-6285 AND |
Lisa Wright 859-323-6921, |
|
If NO response, call Security |
Chris Buford |
|
|
Shawn Skeese cell = 859-333-2754 |
|
|
Derek Crouse |